Overview
This is the large-frame end of the AC axial range: a 120 W motor turning a wide impeller to move air in the thousands of cubic metres per hour. It is used where a cabinet, a small plant room or a machine housing has a heat load that small fans cannot shift, and where the opening can take a full-size unit.
Eight models cover 115 V, 230 V and 380 V at 50 and 60 Hz, with two 380 V winding variants. Airflow runs from 2,280 to 2,570 m³/h and noise from 65 to 70 dB(A); the higher figure belongs to the 60 Hz version, which turns faster.
Where it fits
- Large control cabinets, drive panels and power distribution enclosures
- Small plant rooms and technical spaces with a concentrated heat load
- Machine and process housings that need bulk air movement
- Wall or frame mounting where a full-size opening is available
Specifications
| MODEL | Voltage (VAC) | Frequency (Hz) | Current (AMP) | Power (W) | Speed (RPM) | Air Flow (m3/hr) | Air Flow (CFM) | Noise Lp:dB(A) | Weight (kg) |
|---|---|---|---|---|---|---|---|---|---|
| HA2808001HB-1 | 115 | 50 | 1.2 | 120 | 2400 | 2280 | 1341 | 65 | 2.803 |
| HA2808001HB-2 | 115 | 60 | 1.2 | 120 | 2500 | 2570 | 1512 | 70 | 2.803 |
| HA2808002HB-1 | 230 | 50 | 0.55 | 120 | 2400 | 2280 | 1341 | 65 | 2.803 |
| HA2808002HB-2 | 230 | 60 | 0.55 | 120 | 2500 | 2570 | 1512 | 70 | 2.803 |
| HA2808003HB-1 | 380 | 50 | 0.32 | 120 | 2400 | 2280 | 1341 | 65 | 2.803 |
| HA2808003HB-2 | 380 | 60 | 0.32 | 120 | 2500 | 2570 | 1512 | 70 | 2.803 |
| HA2808003HB-3 | 380 | 50 | 0.36 | 120 | 2400 | 2280 | 1341 | 65 | 2.803 |
| HA2808003HB-4 | 380 | 60 | 0.36 | 120 | 2500 | 2570 | 1512 | 70 | 2.803 |
Selection and installation notes
At this size the mounting structure matters: the fan transmits vibration into thin panels and the noise is carried through the wall. Use anti-vibration mounts and a rigid frame, and plan the exhaust free area to match the intake.
The 380 V models include two winding variants with different current draw (0.32 A and 0.36 A). Confirm the supply and protection before ordering; the airflow and power are the same, but the starting current and wiring differ.
FAQ
What is this fan used for?
Moving bulk air through large cabinets, drive panels and small plant rooms where the heat load is too high for compact fans and a full-size opening is available.
Which voltages are available?
115 V, 230 V and 380 V at 50 and 60 Hz. The 380 V range includes two winding variants with different current draw.
How loud is it?
65 dB(A) at 50 Hz and 70 dB(A) at 60 Hz at one metre. Plan the mounting and the room, not just the fan, if noise is a constraint.
Does it include a guard?
The fan is supplied as a unit; guards and mounting accessories are selected separately. Tell us the mounting position and we will confirm the guard that fits.
Request Quote
Interested in this product? Share your requirements or questions using the form.
-
Your requirements
Include the specifications, options, or quantity you need, if known.
-
Your questions
Ask about product details, availability, or order information.
-
Your contact details
Leave an email address where you can receive a reply.